Environment Monitoring System IP Temp CAT5 Video Extender HDMI VGA DVI KVM Switch, Video Splitter, Video Matrix Switch

AC Voltage Detector with Relay, NEMA 5-15 plug

NTI Part #: E-ACVDRLY-515
E-ACVDRLY-515
E-ACVDRLY-515
NTI Part #: E-ACVDRLY-515
Monitor the presence or absence of line voltage.
  • ROHS Compliant AC Voltage Detector with Relay, NEMA 5-15 plug
  • CE Compliant AC Voltage Detector with Relay, NEMA 5-15 plug

Overview

  • Measurement range: detects mains voltage from 50 to 250 VAC.
  • Measurement indication: Alarm or Normal.
  • Sensor type: open/closed contact switch.
  • Includes internal relay.
    • Maximum close voltage: 90VAC @ 60Hz, 108VAC @ 50Hz
    • Minimum open voltage: 10VAC @ 60Hz, 12VAC @ 50Hz
  • Includes 6-foot (1.8-meter) 2-wire cable to connect to the ENVIROMUX system.
  • E-ACVDRLY-515: Standard US 120V 10A NEMA 5-15 plug on attached 5.5-foot (1.67-meter) cord.
  • Operating temperature: 32 to 140°F (0 to 60°C).
  • Storage temperature: 32 to 158°F (0 to 70°C).
  • Operating and Storage Relative Humidity: 17 to 90% non-condensing RH.
  • Regulatory approvals: CE, RoHS
  • Compatible with E-1W.